9Section 61150043L1-5, Issue C61150043L1-5C
D. Release the case support by turning the fastener
counter-clockwise and tilt the circuit pack
support structure to expose the surge arrestors
on the bottom. List 1 and List 2 Repeater
Housings contain 16 surge arrestors.
E. Grasp one surge arrestor and remove it using
the Insertion/Extraction Tool; see Figure 9.
F. Place a replacement surge arrestor in the
same position.
G. Replace the remaining surge arrestors in the
same manner.
H. Close the circuit pack support structure;
secure by turning the fastener clockwise.
I. Reseat the tagged powering modules at the
central office.
J. Perform circuit tests to verify proper circuit
operation.
K. Remove the tags on the powering modules.
L. Replace the O-ring if it has not been replaced
within the last three months.
M. Reattach the dome and locking clamp then
repressurize the Repeater Housing. See the
subsection entitled “Installation,”
instructions F through I.
4. WARRANTY AND CUSTOMER SERVICE
ADTRAN will replace or repair this product within
five years from the date of shipment if it does not
meet its published specifications or fails while in
service (see ADTRAN Equipment Warranty,
Repair, and Return Policy and Procedure).
Return Material Authorization (RMA) is required
prior to returning equipment to ADTRAN.
For service, RMA requests, or further information,
contact one of the following numbers.
ADTRAN Customer Service:
ADTRAN Telco Technical Support. (800) 726-8663
Standard support hours ..................... Monday-Friday
7 a.m. - 7 p.m. CST
Emergency support ......... 7 days/week, 24 hours/day
Sales.................................................. (800) 827-0807
Customer and Product Support ........ (256) 963-8722
Repair and Return Address:
ADTRAN, Inc.
Customer and Product Support (CAPS) Department
901 Explorer Boulevard
Huntsville, Alabama 35806-2807
Replacement of Surge Arrestors
NOTE
Electrical shock can occur if modification or
surge arrestor replacement is attempted before
removing the powering modules.
If lightning is the suspected cause of circuit pack
failure, ADTRAN recommends replacing all surge
arrestors within the Repeater Housing. Figure 9
shows the surge arrestors on the bottom of the
circuit pack support structure.
To Replace Surge Arrestors:
A. Unseat and tag the appropriate powering
modules (located in the central office) before
replacing surge arrestors inside the Repeater
Housing. This removes power from the wires
and pins. The tag should read, “Do not insert.
Field work in process.”
B. Release pressure in the Repeater Housing by
depressing the needle in the fill valve; see
the subsection entitled “Installation,”
instruction C, and Figure 3.
C. After cleaning debris from the dome and clamp,
remove the clamp and dome; see the subsection
entitled “Installation,” instruction D.
Figure 9. Replacing Surge Arrestors
Comentarios a estos manuales